Deep Sea DSEG4500 Compact Single Genset Controller Remote Start Controlling Module AMF Part Made in UK Replacement DSE4520/4620
Deep Sea DSEG4500 Compact Single Genset Controller Remote Start Controlling Module AMF Part Made in UK Replacement DSE4520/4620
無法載入取貨服務供應情況
The DSEG4500 Compact Single Genset Controller and DSEG4501 Compact Single Genset Controller with RS485 are part of the next-generation DSEG-Series platform, designed for versatility and performance. User-configurable for Remote Start (RS) or Automatic Mains (Utility) Failure (AMF) applications, they offer a robust feature set tailored to single genset operations.
Selected features include real-time monitoring of generator and load power, engine speed, oil pressure, coolant temperature, frequency, voltage, current, power, and fuel level. All critical data is displayed on a dedicated multi-line, text and icon high-resolution screen.
OVERALL SIZE:142.6 mm x 118.6 mm x 48.5 mm / 5.61 ” x 4.66 ” x 1.91 ”
PANEL CUTOUT SIZE:118 mm x 92.0 mm / 4.65 ” x 3.62 ”
MAXIMUM PANEL THICKNESS:5 mm / 0.19 ”
Key Features
Designed to protect and control a genset, genset breakers and mains (utility) breaker
Remote Start / AMF functionality in one controller
Wide range of control and protection features
Flexible connection and communication options
Multiple configuration possibilities
Simple user interface control
Integrated gasket (IP65 protection)
Separate FPE PIN and maintenance reset PIN
Manual front panel and automatic control modes
Module status pages for both current (DM1) and previous (DM2) Diagnostic Trouble Codes
Event logging for current (DM1) Diagnostic Trouble Codes
Specification
DC Supply
CONTINUOUS VOLTAGE RATING: 8 V to 35 V DC continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 10 V. This is achieved without the need for internal batteries. Backlight will not be maintained during cranking.
MAXIMUM OPERATING CURRENT: 200 mA at 12 V, 120 mA at 24 V
MAXIMUM STANBY CURRENT: 65 mA at 12 V, 35 mA at 24 V
CHARGE ALTERNATOR EXCITATION / FAIL RANGE: 0 V to 35 V
Inputs
ANALOGUE
Number: 3
Type: Negative Switching Digital Input, Resistive Analogue Input, Current Analogue Input or Voltage Analogue Input
DIGITAL
Number: 4
Type: Negative Switching Digital Input
MAGNETIC PICK-UP INPUT
Voltage Input Range: 0.5 VPeak to 70 VPeak
Frequency Input Range: 1 Hz to 10 kHz
Outputs
DIGITAL
Number: 6
Type: Positive Switching DC Outputs
AUXILIARY SUPPLY OUTPUT
Number: 1
Rating: 20 mA at 5 V
Communications
USB B: 1 Programming Port
CAN:1 CAN Port
Voltage Measurement
NUMBER :2
MEASUREMENT INPUTS: 3 Phase + Neutral
Remote Start Controller: Generator Only
Automatic Mains (Utility) Failure Controller: Generator and Mains (Utility)
VOLTAGE RANGE
15 V to 415 V Phase to Neutral
25 V to 720 V Phase to Phase
FREQUENCY RANGE: 3.5 Hz to 75 Hz
RESOLUTION
1 V Phase to Neutral
2 V Phase to Phase
0.1 Hz
ACCURACY :±1 % Phase to Neutral; ±2 % Phase to Phase; ±0.05 Hz
Current Transformer Measurement
NUMBER:3
MEASUREMENT INPUTS
Remote Start Controller: Generator Only
Automatic Mains (Utility) Failure Controller: Generator or Load
CURRENT RANGE:0 A to 5 A
RESOLUTION:0.5 %
ACCURACY:±1 %

Ying
分享